Abstract
AbstractThis paper considers the problems of automatic correction of systematic error appearing in conventional Automatic Generation Control (AGC) regulators, due to the ignorance of power losses, normally existing on all inter‐area tie‐lines. This is achieved with modification of input signals on AGC area regulators (the Area Control Error, ACE) by introducing the tie‐line losses, calculated by simple measurements of all area tie‐line flows at both (sending and receiving) line ends. The paper presents the theoretical development of the idea and proposes the new, modified, but cheap AGC scheme, proven by simulation tests on the example of two‐area interconnection. The benefit of applying the proposed AGC regulators is the better system performance and less frequent need for the synchronous time and inadvertent interchange error corrections. Copyright © 2007 John Wiley & Sons, Ltd.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.