Abstract

Partial discharge (PD) signals acquired from on-line measurements of power transformers are easily overwhelmed by various interference and noise. This paper proposes an automatic blind equalization (BE) and morphological thresholding method for PD signal de-noising. Firstly, BE automatically selects an equalized signal that reveals PD impulses from an acquired noise-corrupted signal. Then, automatic morphological thresholding (AMT) is adopted for determining thresholds on the equalized signal. After de-noising with BE and AMT, phase-resolved pulse sequence (PRPS) is constructed and used for analyzing the types of insulation defects that cause discharges. To verify the proposed method, PD measurements on experimental PD models and a distribution transformer have been conducted. The results show that PD impulses can be extracted from severely noise-corrupted signals by using the proposed method. Also, PRPS constructed from de-noised signals can achieve consistency in revealing the types of insulation defects even different types of PD sensors and measurement systems are used.