Abstract

For installation in the public electric power grid of the city of Augsburg, Germany, a resistive superconducting fault current limiter (SFCL) was designed, constructed, tested and operated in the framework of a partially funded project ‘ASSiST’. Right from the beginning, it was agreed to aim for a prolonged operation even after closure of the project. This endeavor has been started due to a fundamental need to limit the prospective fault currents at a feeder point of the grid and in order to create long-term operational experience on a device seamlessly integrated into commercial grid components and switchgear, thus demonstrating a high level of readiness for widespread application. It revealed that the SFCL was of robust design – withstanding all electrical tests including a special two-phase fault and sustaining stable cryogenic conditions even during partial outages of the cooling system – and that the technology is reducing loss by shunt reactors. Furthermore, due to the control equipment on medium voltage level, valuable insights on grid behavior could be gained. The extended operation for 4 years has clearly shown the performance and robustness of SFCL technology in feeder points on MV level and provides a reference point for further commercialization.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call