Abstract

One of the most important aspects of working in an office environment is ensuring that the space has optimal thermal comfort and an indoor environment. The aim of this research is to investigate the thermal comfort and indoor climate in three office rooms located at one of the campus buildings at the University of Gävle, Sweden. The evaluated period is in the month of April during springtime. During this period, parameters such as temperature, relative humidity, CO2, supply air flow rate, and room air velocities are measured on site. The results of the measurement show that the indoor temperature is on average lower in the rooms facing north, at 21–23.5 °C, compared to the rooms facing south, which reach high temperatures during sunny days, up to 26 °C. The results also show that the ventilation air supply rate is lower than the requirement for offices in two of the office rooms. The ACH rate is also low, at ≈ 1 h−1 for all the rooms, compared to the required levels of 2–4 h−1. The CO2 levels are within the recommended values; on average, the highest is in one of the south-facing rooms, with 768 ppm, and the maximum measured value is also in the same room, with 1273 ppm for a short period of time.