Abstract

In this study, the operating conditions of the tri-generation model in actual field situations for terminal complex buildings were investigated. The operational characteristics of the installed tri-generation system (TGS), and performance in terms of relative primary energy savings (RPES), were evaluated to confirm its market competitiveness against separate heat and power (SHP). As a result of the analysis, the technological superiority of the TGS model compared to the SHP method was much lower than theoretical expectation, which was 17.9% in the best case and close to 0 in the worst case. The importance of the TGS’s operational strategy to achieve annual operational economics was emphasized based on the analysis of the TGS’s actual daily operational data. The sustainability of the TGS model in the era of climate change was also evaluated through RPES sensitivity analysis according to the level of renewable power generation in the power sector, which is rapidly increasing in response to climate change.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.