Abstract
Fire tests have been conducted with TDI under conditions simulating a pool fire originating, e.g. from a leakage of stored TDI. The facilities of Cerchar * provide conditions of a free-burning, well-ventilated fire. Burning rate, heat and smoke development and toxic gas emission were determined as a function of the pool diameter up to 1 m2. Results are compared with small scale test results. Burning rate increases with increasing pool diameter reaching 2 kg/m2-min at 1 m2 area. Yields of permanent gases do not differ significantly with increasing pool area, with HCN amounting to 5 mg/g. Free TDI is found in fire gas up to 15 ppm corresponding to a yield of 7 mg/g.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.