Abstract

The aim of this study was to evaluate the operation of a stationary air purifier under the model conditions of a non-occupied test chamber with dimensions similar to a typical living room. The purifier was equipped with a system for neutralization of volatile organic compounds, disinfection (neutralizing chamber with a system of UVA lamps, plates made of TiO2, UVC lamp settings) and HEPA filters at the air outlet of the device. The conducted research focused on the effectiveness of removing bacterial bioaerosols (M. luteus and B. subtilis) as well as formaldehyde and the sum of volatile organic compounds. The assessment was made for two ranges of fan flow, 100 and 300 m3 / h (Standard and Turbo). The unit shows high efficiency in removing the tested bacterial strains, i.e. 100% after 60 and 90 minutes, respectively. Higher efficiency occurred for lower fan output. However, its effectiveness in removing TVOCs did not exceed 58%. Additionally, the formation of formaldehyde was noted during the operation of the purifier.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.