Abstract
A study was performed to investigate the use of computational fluid dynamics (CFD) coupled with a fluence rate model to determine the bias in UV biodosimetry measurements using inactivation of a challenge microbe instead of the target pathogen—termed the reduction equivalent fluence (REF) bias. Simulations were performed using two fluence rate models: RADial Line Source Integration (RADLSI), and UVCalc3D, a multiple segment source summation (MSSS). CFD UV models were carried out in several closed-conduit UV reactors using either mono- or polychromatic lamps. Simulations were also performed with different UV transmittances, flow rates, lamp power settings, and with lamps out of service. In addition, the Cryptosporidium fluence response kinetics was approximated using two nonlinear models: a P-factor model, and a Rational model. The REF bias was computed using the predicted fluence distribution from a Lagrangian particle tracking routine and compared with the REF bias computed using the EPA UV disinfection ...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.