Abstract

In Sweden, around 10% of the energy supplied to the district heating networks are lost through heat losses from the distribution pipes. In cylindrical geometries it is preferable to improve the insulation as close to the center as possible. This has resulted in a hybrid insulation district heating pipe concept with a combination of vacuum insulation panels at the center, held in place by polyurethane foam. In the twin pipe concept, the vacuum insulation panel cover the supply pipe. This creates a complex temperature profile over the section and measured results on single pipes might not be applicable. Therefore, there is a need for a method to evaluate the improvement of hybrid insulation twin pipes in the laboratory. This paper presents a method where two guarded hot pipe apparatuses is used, one heating rod for each pipe, to measure the heat losses from hybrid pipes and compare to a conventional polyurethane pipe. The measurements indicate an improvement in thermal performance by 12%-18% for the total losses and by 29% -39% for the supply pipe losses.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.