Abstract
Single-phase arcing ground fault is the main fault for the distribution work system, which brings great threat to power system. For this reason, this paper conducts a study on arc fault and focus on arc modeling and its effect on fault characteristics. Cassie-Mayr arc model is selected to describe grounding arcing characteristics. The ground model is set up and the typical voltage-ampere characteristic curve is obtained. Furthermore, the simulation results show that the V-I is influenced by the arc model and arc parameters. The parameters of the arc modeling are determined according to the structure features of the distribution network. Compared with individual Cassie arc model, Mayr model and constant resistance model, the simulation results using by Cassie-Mayr arc model are closer to practice, which demonstrates the validity and correctness of the model.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.