Abstract
The arc-fault is the main reason that cause electric fires. The technology of arc-fault circuit interrupters (AFCI) is the new circuit protection technology and it could avoid arc-fault causing fire effectively. The appearance of arc-fault can not be predicted. The traditional time domain or frequency domain analysis method for arc-fault signal processing is not ideal because it’s inaccurate and not in time. This paper bases on characteristics of arc-fault signals and analyzes the series connection arc-fault signal by Daubechies wavelet transform in 4 orders. As a result, it can provide the characteristics of arc-fault and detect arc-fault effectively and timely. This method is confirmed reliability by the simulation result and provides the theoretical basis of the development of AFCI.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.