Abstract

This paper presents a two-level hierarchical control structure for biological wastewater treatment plants, with the goal of improving effluent quality and reducing operational costs. The Benchmark Simulation Model No. 1 is used as working scenario. The hierarchical structure allows to adjust the dissolved oxygen in the fifth tank (SO,5) according with the working conditions, instead of keeping it in a fixed value. Model Predictive Control (MPC) with inlet flow rate feedforward control (MPC+FF) is proposed for the lower level to control nitrate nitrogen concentration of the second tank and SO,5. MPC, Affine Function and fuzzy controller are tested for the higher level to adjust the SO,5 set point of the lower level based on the ammonium and ammonia nitrogen concentration in the fifth tank. Modifying the tuning parameters of the higher level, a tuning region is determined, in which the effluent quality and operational costs are simultaneously improved.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.