Abstract

Historically, Class A ground-fault circuit interrupters (GFCIs) have been responsible for a substantial reduction in residential electrocutions. Yet, they have not had much success in industrial applications because of the limitation on system voltage (maximum 240 V) and the 6 mA maximum allowed leakage current. As a result, industrial personnel protection has been lagging its residential counterpart. UL realized this gap and defined new GFCI classes to specifically address personnel protection in industrial applications. The new UL 943C defines the requirements of special-purpose GFCIs that can be used on systems up to 600 V and allows for a leakage current of 20 mA. This paper describes the UL 943C requirements and the newly defined GFCI classes. The difference between equipment ground-fault protection devices (EGFPDs) and GFCIs are also addressed. Finally, the application of a Class C GFCI in a pulp and paper plant is described.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.