Neutron noise measurements were carried out on Boiling Water Reactors (BWRs) of Tarapur Atomic Power Station (TAPS), using local power range monitors (LPRMs). These measurements were carried out to develop applications of noise analysis for detection of vibrations of instrumentation tubes, transit times of two phase flow and for monitoring the health of LPRMs. 16N noise signals were also used for the determination of coolant flow rate in the recirculation loop of TAPS Unit I. Additionally, neutron noise measurements were also carried out at low powers during the commissioning of Unit I of Madras Atomic Power Project (MAPP), Pressurized Heavy Water Reactor (PHWR). This paper presents the measurements that were made.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.