Abstract

In order to remain economically effective and financially profitable, the modern industries have to take their safety culture to a higher level and consider production losses in addition to simple accident prevention techniques. Ideally, compliance with safety requirements start during early design stages, but in some older facilities provisions for Safety Instrumented Systems (SIS) may not have been originally included. In this paper, a case study of a Reheater Drains (RD) system is used to illustrate such an example. Frequent failures of tank level controller lead to transients where the operation of shutting down RD pumps requires operators to manually isolate the quenching water and to close the main steam admission valves. Water in this system is at saturation temperature for the reheater steam side pressure, and any manual operation of the system is highly undesirable due to hazards of working with wet steam at approximately 758kPa(g) pressure, preheated to 237°C. Additionally, losses of inventory are highly undesirable as well and challenge other systems in the plant. In this paper, it is suggested that RD system can benefit from installation of an independent SIS system in order to address current challenges. This idea is being explored using IEC 61508 framework for “Functional safety of electrical/electronic/programmable electronic safety-related systems” to provide assurance that the SIS will offer the necessary risk reduction required to achieve required safety for the equipment.