Abstract

Powell’s optimization method has been used for the evaluation of the surge arrester models parameters. The proper modelling of metal-oxide surge arresters and the right selection of equivalent circuit parameters are very significant issues, since quality and reliability of lightning performance studies can be improved with the more efficient representation of the arresters’ dynamic behavior. The proposed approach selects optimum arrester model equivalent circuit parameter values, minimizing the error between the simulated peak residual voltage value and this given by the manufacturer. Application of the method in performed on a 120 kV metal oxide arrester. The use of the obtained optimum parameter values reduces significantly the relative error between the simulated and manufacturer’s peak residual voltage value, presenting the effectiveness of the method.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call