Conventional ferromagnetic core current transformer (CT) is widely used to measure large alternating currents with lower rated instrumentations or ammeters. The improper choice of the load of secondary instrumentations (symbol in Z L , e.g., relay protection apparatus) will negatively influence the measurement accuracy. Testing Z L and multiple of current in the case of 10% error of current m 10 , and thus plotting the relationship between Z L and m 10 , is helpful to give valuable instructions for properly choosing the secondary instrumentations. The principle of calculating values of Z L and m 10, methods of operation of acquired data to determine key parameters, and technique to fit the curve m 10 -Z L resorting to least square estimator are presented. Hence the curve m 10 -Z L can be successfully plotted based on polynomial coefficients of fitting curve. Experimental results verify the validity of the proposed method, which removes most of the noise of the data, smoothes the curve, and hence increases the measurement accuracy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.