Abstract
A hot line tan delta measuring apparatus which uses the secondary voltage of GPTs (grounding potential transformers) existing at substations and other facilities has been developed. An error vector circle diagram method which allows one to determine the value of tan delta to an accuracy of 0.1%, notwithstanding the phase difference existing between the primary and secondary voltages of a GPT, is described. The method was used in field experiments with favorable results. The method is especially superior in terms of safety and operability because no contact with high-voltage portions is required.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.