Abstract

Power transmission tower is an important part of power transmission equipment. The tower foundation is suffered by landslides, debris flows, erections of foundation settlement and so on. The power transmission tower near Yanjin transformer substation is selected to be measured. By using fiber Bragg grating (FBG) earth pressure sensor, the earth pressure of tower foundation is measured. The long-term monitoring data indicate that the #1 sensor daily variations amplitude of earth pressure is 7.22KPa, and the #2 sensor daily variations amplitude of earth pressure is 4.69KPa. In the 479 days, the rangeability of average data is 61.55KPa in sensor #1 and 64.05KPa in sensor #2. Compared with the local precipitation, the earth pressure of tower foundation is seasonal change. According to the history data, the warning threshold value is set as 280KPa.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.