Abstract

Aiming at the problems of large delay and poor anti-disturbance ability in the outlet temperature control system of the heat exchanger to optimize the control accuracy of the system and improve the control performance, this paper proposes a control scheme combining predictive functional control with proportional-integral-derivative control. Using the incremental proportional-integral-derivative control algorithm to improve the optimization objective function of the predictive functional control algorithm, a predictive functional control optimization model with a proportional-integral-derivative structure is established. The feedforward compensation control is adopted to eliminate the influence of external disturbances on the heat exchanger temperature control system. Through simulation, the proposed control scheme is compared with the feedforward cascade compound control scheme based on a proportional-integral-derivative main controller. The results show that the scheme has a small over harmonic and strong anti-interference ability. The adaptability and stability of the system are significantly improved, and the exit temperature of the heat exchanger can be effectively controlled.