Abstract
To develop a GIS fault location system, a series of development tests were carried out, including arc tests, using actual apparatus. As a result, a system was developed, using pressure wave, gas pressure, optical, vibration, and grounding wire current sensors. These sensors were applied according to the features of equipment structures. While studying important factors in applying fault location sensors, the system was developed while paying particular attention to methods for detecting circuit breaker faults in resistance-grounded substations. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.