Abstract

The results of research into the possibility to use coaxial cable lengths for protection of capacitors in large capacitor banks are presented. The pulsed current value permissible for cables in normal operation is estimated in view of the strength of the outer conductors under the action of electrodynamic forces. The motion of the outer conductors and cable sheath caused by electrodynamic forces arising in the emergency modes at capacitor breakdown was observed. The experiments revealed that the outer conductors disintegrate in the emergency modes because of overheating, softening, and subsequent break of the outer conductors in the points of interlacing and electrical contacts between these conductors. It was found that the polyethylene sheath of the cable provides conditions for arc extinction and current interruption in emergency modes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.