Abstract

This paper presents a digital distance relay scheme for power transmission line protection. The scheme uses a single criterion to determine the fault distance during the ten types of shunt faults on a three-phase transmission line. The criterion is derived using a modal transformation. The scheme uses a recently developed algorithm based on block pulse functions to compute fundamental frequency voltage and current phasors of fault signals. The scheme is tested using simulated voltage and current signals obtained from the electromagnetic transient program (EMTP). These simulations are performed on a 230 kV transmission line of a six bus power system model.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.