Abstract

Long-distance XLPE cable lines were laid over a distance of 26.9 km using the newly established 275 kV XLPE cable technology and in-situ jointing technique. Field AC HV withstand testing was conducted on these lines as the after-laying test-the first such test for long-distance EHV XLPE cable lines. For this test, small resonance type AC withstand HV test equipment was developed. A new system was also established for direct and simultaneous measurement of partial discharge over the entire cable length. One latent defect was detected in this test, proving that the test method is extremely effective in confirming the quality of XLPE cable lines.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.