Abstract
The influence of harmonics on commonly used three-phase watthour and kVA demand meters was studied using a computer-controlled three-phase test system capable of generating nonsinusoidal voltages and currents. A description of the three-phase test system and results of preliminary tests of several revenue meters are presented. The performance of the tested meters is compared with the response of time-division and thermal reference meters for different harmonic conditions, primarily field-recorded data. Errors up to 2% were observed during the testing of energy meters and up to 35% for kVA demand meters.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.