Abstract

The penetration of wind turbine generators onto the grid has grown worldwide at unprecedented rates in recent years. This raises the concern that the tripping of wind turbine generators could potentially cause system collapses. To alleviate these concerns, wind turbine generators need to maintain connection with the grid when a grid fault occurs. This has provoked many countries to adopt low-voltage ride-through (LVRT) for wind turbine generators. The LVRT is the capability of wind turbine generators to maintain connectivity during certain periods of voltage sag. The wind turbine generators should be connected to the grid to support fault recovery. Also, wind turbine generators must provide reactive power according to the grid voltage sag. Therefore, much research has been focused on enhancing LVRT capability. To enhance LVRT capability, this paper proposes the application of a superconducting fault current limiter (SFCL) in the system. The fault current was suppressed and the voltage sag was improved through the application of the SFCL. By improving the voltage sag, the wind turbine generator and the grid were able to maintain a connection. However, suppression of the fault current can cause a problem in the overcurrent relay (OCR) trip time delay. The trip time delay was solved by OCR resetting. Through a power system computer-aided design/electromagnetic transients including DC (PSCAD/EMTDC), the enhancement of LVRT capability and improvement of the trip delay was confirmed.

Highlights

  • Over the past few years, wind power, as a source of renewable energy, has grown rapidly in many countries [1]

  • In case of the fault corresponding to area A, the wind turbine generators must maintain the connection with the grid

  • The purpose of enhancing low-voltage ride-through (LVRT) capability is to maintain the connection between the wind turbine generator and the grid for recovery of the fault voltage

Read more

Summary

Introduction

Over the past few years, wind power, as a source of renewable energy, has grown rapidly in many countries [1]. The traditional wind turbine generators connected to the grid were usually disconnected when grid faults occurred. In case of the fault corresponding to area A, the wind turbine generators must maintain the connection with the grid. In the event of the fault corresponding to area C, the wind turbine generators and the grid are disconnected [3,4,5]. When the grid voltage is out of the normal range, the wind turbine generators must supply reactive power to the grid according to the voltage sag rate [3,4,5]. The purpose of enhancing LVRT capability is to maintain the connection between the wind turbine generator and the grid for recovery of the fault voltage. When a grid fault occurs, the converter may be out of the control [12,17,18]

Method for enhancing the LVRT capability
Simulation Modeling
Superconducting Fault Current Limiters
Overcurrent Relay
Case without SFCL
Case with an SFCL
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call