Abstract

An 800 kV metal oxide transmission line surge arrester (TLA) has been developed, installed, and tested on the AEP 765 kV Marysville to Kammer transmission line. The purpose of this transmission line surge arrester (TLA) is to pave the way for the development, construction, and application of an 800 kV SF6 dead tank circuit breaker without closing resistors and free standing current transformers at AEP's 800 kV Orange station. The maximum design operating voltage is 800 kV, and 765 kV is the nominal operating voltage. Successful field test results of the TLA's ability to limit switching overvoltage emanating from circuit breaker operation to below the transmission line switching withstand are given. Successful test results of the 800 kV dead tank circuit breaker design dielectric test are given.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.