Abstract

AC/DC hybrid power grids are more and more widely used in China, and the traditional relay protection directional components have experienced multiple misoperations. The adaptability of traditional directional components in AC / DC hybrid power grids is studied. Traditional direction components are based on fault sequence component network analysis. During the fault, the positive and negative sequence impedance of the AC-DC hybrid power grid is quite different, and the impedance angle of the line impedance and the equivalent impedance of the grid is no longer close to 90°. Misjudgment will occur in the direction component with sudden change, and performance cannot be guaranteed. As a result, directional elements based on the positive and negative sequence current branching coefficients being approximately equal are not suitable for AC/DC hybrid power grids. As for the directional element of the zero sequence principle, since the zero sequence network on the inverter side is relatively stable, its performance is reliable and it can operate correctly.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.