Abstract
In practical engineering, air-cooled heat exchangers are commonly equipped with middle, left, or side water entry arrangement, and in winter may be at risk for freezing. This research studies the water flow and the exit water temperature distributions of tubes in different rows and passes, and explores the anti-freezing characteristics for air-cooled heat exchangers with these three typical water entry patterns. The micro-volume transport model is adopted to more accurately determine the air/water-side thermo-flow performance of finned tubes. The results show that air-cooled heat exchangers with different water entry patterns have different water flow distributions that induce different exit water temperature distributions. However, water entry patterns have little impact on the anti-freezing performance of air-cooled heat exchangers because the minimum exit water temperature is not significantly changed. Exit water temperatures of windward row 1 tubes, especially those near the header region of an air-cooled heat exchanger with a middle-type header and far from the header region of an air-cooled heat exchanger with a left/side header, are suggested for monitoring at dry-cooling power plants.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.