Abstract

Coal mining is one of the important economic sectors in Vietnam. Power supply systems of coal mines and open-cuts are complex. They have multiple levels of voltages and different types of loads. New electrical equipment usually works alongside with the equipment that is obsolete and worn-out. Power supply systems of industrial areas of Vietnam where coal is mined are characterized by the low power quality. In Vietnam the indices which characterize the distortion of both voltage and current waveforms have standard values. The article presents the findings upon the analysis of a power supply system of a coal open-cut in Vietnam and the electrical equipment of the coal sorting plant along with the results of the experimental studies of power quality indices and the non-sinusoidal mode parameters. The measurement analysis has shown that the indices of the 5-th and 7-th harmonics of voltage were over the limits. There are interharmonics in voltages and currents. The article analyzes the characteristics of active filters. It is possible to improve the power quality by using an active filter which generates both reactive power to increase the load power factor and harmonic and interharmonic currents to reduce the degree of voltage and current waveform distortion.

Highlights

  • Coal mining is one of the important economic sectors in Vietnam

  • Power supply systems of industrial areas of Vietnam where coal is mined are characterized by the low power quality

  • This article analyzes a power supply system scheme of one of the coal open-cuts in Vietnam, its loads, the power quality based on the measurements of power quality indices and harmonics mode parameters

Read more

Summary

Introduction

Power supply systems of coal mines and open-cuts are complex They have multiple levels of voltages and different types of loads. In Vietnam the indices which characterize the distortion of both voltage and current waveforms have standard values specified in [2, 3]. This article analyzes a power supply system scheme of one of the coal open-cuts in Vietnam, its loads, the power quality based on the measurements of power quality indices and harmonics mode parameters. It analyzes the characteristics of active filters that could be used to improve the power quality in the coal opencut

Power supply system of a coal opencut
Results of the power quality and mode parameters measurement
Results of the active and reactive power measurement
Results of voltage harmonics measurement
Results of voltage and current interharmonics measurement
Characteristics of active filters
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.