Abstract

Analytical expressions are derived to gain insight in the operating principles of phase shifting transformers (PSTs) in a highly meshed grid. To this extent, the dc load flow algorithm is adapted to account for such devices. This leads to a linear expression for the relation between PST settings and the active power flow in the lines. Based on these equations, the total transfer capacity (TTC) can be described mathematically, which allows for optimization. Furthermore, the linear least squares method is used to distribute a cross-border transport evenly over the interconnectors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.