Abstract

Analysis the wiring of head and tail pully driving & bidirectional 6KV motor,and found the reason of negative phase sequence over current protection malfunction did occur when the motor ran in the reverse direction , then compared the solution methods to make sure which one is better. At last use the method that change the sampling program to make the motor negative phase sequence over current protection wil in effect.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.