Abstract
An a.c./d.c. full-controlled converter with a few damaged power switches can still be operated with deteriorated output performance and may temporarily be used to supply part of the load. In this paper, the output characteristics of a partially damaged converter are investigated by employing the derived switching functions. These switching functions can easily be implemented to formulate the resultant output waveforms and calculate the effective output voltages for all possible fault cases. Based on these switching functions, the operating characteristics of the abnormal full-controlled converter can be calculated for the operations of both continuous and discontinuous load currents. Finally, experimental results obtained from a battery charging system are exhibited to validate the simulation results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.