Abstract

There is an air leakage threshold under certain condenser heat load and air ejector output. When the amount of air leakage is less than the threshold, the condenser pressure is essentially the same, we can maintain a stable condenser vacuum, once exceed the threshold, condenser pressure begin to gradually larger, condenser vacuum will deteriorate. Considered the air leakage influences on the heat transfer coefficient of condenser, this paper had been established the one-dimensional steady-state heat transfer model of condenser to obtain the condenser pressure curve along with the amount of air leakage, the turning point on the curve is the air leakage threshold.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.