Abstract

Transient processes are generated by operations of disconnect switches and circuit breakers in the AC side of converter stations. Several trips in different plusmn500-kV HVDC converter stations in china happened recently. Characteristics of transient Electromagnetic Interference due to switching operations are summarized based on onsite tests in a practical converter station. Measurements are performed to analyze the propagation mechanism of transient processes due to variable switching operations. The EM noises generated by switching operations in secondary systems especially the measuring system are analyzed as well. The high frequency characteristics of DC shunts, which is the most important path for EM noise propagation, is analyzed based on tests and calculation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.