An SFCL(Superconducting Fault Current Limiter), which has zero impedance characteristic, doesn"t have power loss and limits fault current quickly, therefore it plays a rule as a protective equipment. And there are many types of SFCLs. In this paper, we analyzed operating characteristics of a double quench SFCL with a transformer. When a fault current flows on this SFCL, a HTSC(High Temperature Superconducting) element on primary of the transformer is operated and then a HTSC element on secondary of the transformer is operated. We tested this SFCL according to turn ratio and compared a double quench SFCL with series resistance for the SFCL with a transformer. After experiments, we could confirm fault current limiting characteristics of the SFCL with a transformer according to turn ratio. Also operating characteristics and power burden of HTSC element according to application for series resistance and for transformer were verified.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.