The coordinated control system of thermal power plant was a multivariable, strong-coupled, nonlinear, big inertia and big lag object. By mechanism analysis, based on the statistical analysis of real operation data, the multivariable simplified differential equation model of boiler fuel flow, turbine governor valve opening and feed water flow versus unit load, turbine pressure and drum water level was constructed. The nonlinearity degree on different load operating point of a 600MW unit was analyzed by using the Gaussian statistics high-order spectrum. The conclusion is that the lower of the load is the more serious the nonlinearity is. It can provide support for the design of fuzzy control, neural network control, calculation, control structure, control parameters and optimization strategy in coordinated control system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.