Abstract

Two stage ammonia-water absorption refrigeration system is applicable for low driving temperature heat source and large temperature lift applications. However, low system performance weakens its advantages because the large heat dissipation brings unacceptable power consumption. Better internal heat recovery is significantly effective for system performance improvement. This paper presents an analysis on maximum internal heat recovery of a mass-coupled two stage ammonia-water absorption refrigeration system by pinch technology. Two sets of freezing conditions are assumed to carry out the analysis. The minimum system heat input and the relevant heat matching are determined by problem table method and grid method. Moreover, the feasible system configurations with optimal energy target are presented under the set conditions according to the grid diagram. The system performance is calculated directly from the problem table. The key point of the maximum internal heat recovery is the heat matching of the streams in the temperature intervals which are adjacent to the pinch point. Compared to a conventional system, the thermal COP of the derived system can be improved by 14.5% and 34.1% under the studied freezing conditions. The improvement is more effective when there is a temperature overlap between the generation and absorption processes.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.