Abstract
The circuit breaker oil and gas pipeline was closely connected with its hydraulic mechanism and SF6 insulation system, and was an important accessory related to the mechanism’s power and insulation performance. Aiming at the current high-pressure tubing fracture of the oil and gas pipeline of the circuit breaker, the cracking of the SF6 three-way valve interface bolt and the connecting pipe, the chemical composition, mechanical properties, metallographic structure and fracture morphology of each accessory were analyzed from the material point of view, and the material composition was found poor, excessive hardness and abnormal metallographic structure were the main reasons for the failure of circuit breaker oil and gas pipeline components, and technical supervision suggestions had been put forward from the aspects of network check and operation and maintenance inspections.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.