Power quality is closely related to electrical energy which is directly related to voltage and current interference. Electrical equipment used daily requires good power quality. The thing that affects the quality of the power is the voltage dip. Based on the IEEE 1159-1995 standard, voltage sag is a decrease in RMS voltage with duration of 0.5 cycle to 1 minute. Sag voltage that occurs can have an effect on electronic equipment and other problems that often arise in the industrial environment. Therefore, a short circuit fault analysis was conducted to determine the voltage sag based on the type of fault in the sub system in Central Sumatera. Short circuit fault analysis is done using Powerworld Simulator 7.0 Students Edition. This study is intended to determine the sag voltage when there is a short circuit fault. The biggest voltage sag occurs when a short circuit fault of single phase to ground at 75% fault location and the smallest voltage sag when the three-phase short circuit of 0.7 fault location.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical, Energy and Power System Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.