Abstract

The grounding system is very important for lightning protection. If the lightning current is large enough, soil will be ionized, which will have a great effect on the transient performance of the grounding system. In this paper, an efficient time domain method is proposed to analyze the transient performance of the grounding system. The method takes account of nonlinear soil ionization, the shielding effect among electrodes, and frequency-dependent parameters all together. First, a frequency domain circuit model is set up based on a moment method coupling with circuit theory. Then, the model is approximated by a frequency-independent circuit model with the help of vector fitting method. Finally, the time-varying soil ionization is considered by making corresponding parameters time-varying when a time domain method is used to solve the circuit model. The method is validated by field test.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.