Abstract
The Tri-axial high temperature superconducting (HTS) cable usually subjects to the impact of the fault currents in the power system. During the fault, a large amount of the Joule heat is generated, which may be damage cable. In this paper, an analysis model of electromagnetic thermal transient characteristics of the 10 kV/1 kA cable is built. The transient characteristics of the HTS cable are analyzed under a fault current of 15 kA rms lasting 0.14 s, and the current, resistance and temperature of the HTS cable are obtained. The maximum temperature of the HTS cable is 153.1 K under fault current. Meanwhile, the safe operating range of the HTS cable under the fault current of 15 kA to 25 kA is obtained. the analysis results will provide the theoretical basis for the quench protection and relay protection strategy of the tri-axial HTS cable in the Grid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.