Abstract

This article is aimed at quantifying the health condition of the power transformer insulation system through its frequency-domain dielectric characteristic by using the concept of the resistor and fractional calculus. In this regard, the dielectric model of the fractional Poynting–Thomson (PT) is proposed, and a mathematical model for parameter identification of the proposed model is presented. The shuffled frog leaping algorithm (SFLA) is used to realize the parameter identification and the fractional PT model parameters of the oil-paper samples under different insulation health conditions. The influence of moisture and aging on the fractional PT dielectric model parameters is experimentally studied. Results show that, with the increase in the water content within the insulation system, the parameters of the fractional PT model gradually decrease, and there is a strong correlation between the relaxation time and the water content. This facilitates the employment of the fractional PT model parameters to quantify the aging and moisture content of the power transformer insulation system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.