Abstract
It is well known that differential protection is most suitable for transformer protection. However, inrush current due to transformer energization can appear as fault to the protective relay. To improve the security while maintaining the required levels of sensitivity, many restraint methods have been proposed to inhibit operation of the differential element. This paper first will analyze the magnetizing inrush current during transformer energization with a simplified excitation curve. It derives mathematical equations to compute the inrush current based on the residual flux and saturation flux for the worst case energization event. This paper reviews several popular restraint methods used today. A conceptual logic diagram is provided for each method. Advantages and disadvantages of different methods are analyzed for various systems. Finally, using data recorded from real life events and data generated by digital simulations, a performance comparison of different methods is provided.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.