Abstract
Absorption chillers, having thermal compressors, need a heat source at high temperature to obtain cold energy. Because thermal comfort needs are continuously growing, thermal wells placed near cities with high cooling needs might be exploited efficiently all over the year, and the payback time of these systems might be reduced. To investigate the possibility of geothermal energy utilisation for cooling, the parameters of geothermal wells were analysed in the North Great Plain region. From available geothermal wells database, some wells were chosen in order to see which the possibilities are to raise the calculated efficiency value. Based on the repartition of the temperature gradient in Hungarian territory, a diagram was developed in which the efficiency of thermal compressors variation versus well depth is presented. It was stated that deepening the analysed wells with 600–700 m, the efficiency of thermal compressor will be two to three times higher than the original value.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Building Services Engineering Research and Technology
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.