Abstract
While coaxial borehole heat exchangers often have lower borehole thermal resistances than u-tubes, studies in the literature have mixed results as to whether the coaxial design always outperforms the u-tube. This study contributes a systematic comparison between the two designs, accomplished using a custom numerical model in OpenFOAM that provides detailed predictions of the heat transfer within the ground heat exchangers. The modelling and subsequent analysis of system thermal resistances demonstrated that the u-tube and coaxial heat exchanger performances differed the most during the early, transient phase of operation. Furthermore, modelling showed that the coaxial design does not necessarily exceed the u-tube performance long term; testing of coaxial heat exchangers with polyethylene piping showed small differences in outlet temperature compared to the u-tube after 72 h. Additional testing showed that using a steel coaxial outer tube could provide a 22% improvement to performance over the u-tube design. These findings are used to compare predictions of thermal resistance with available analytical models. The impact of the results on the potential for length reductions is also discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.