Abstract

In this paper, aiming at the application of geological disaster monitoring of transmission lines, by analyzing the data quality and positioning accuracy of Beidou original observation data, the influence of the electromagnetic environment of transmission lines on Beidou satellite monitoring data is obtained. According to the Beidou monitoring data of 500 kV transmission line for 23 days, the analysis results show that: in the case of strong electromagnetic interference/no electromagnetic interference, the difference of data integrity is less than 1%, the difference of multipath effect is less than 0.1 m, the difference of signal-to-noise ratio is less than 0.3 dB Hz, and the difference of cycle hop ratio is less than 150. The relative difference in positioning accuracy is less than 5%. In general, the electromagnetic environment of transmission lines has no significant impact on the data quality and positioning accuracy of Beidou deformation monitoring.