Abstract

This paper deals with a 50-MW self-commutated back-to-back (BTB) system intended for power-flow control between two ac transmission networks. It focuses on the dynamic behavior of the BTB system during single-line-to-ground and double-line-to-ground faults. Attention is particularly paid to the dc magnetic flux deviation in the grid and converter transformers, and the circulating current inside the grid transformers, which would produce undesirable effects on the system. Theoretical equations related to the amount of circulating current and the dc magnetic flux deviation are derived. The theoretical results developed in this paper are confirmed by computer simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.