Abstract

Based on periodic solutions of the dimensionless heat conduction equations, an analytical model is developed to study the direct gain passive heating concept for non-conditioned buildings. The effect of multireflections inside the building has also been taken into account. Numerical calculations are also carried out for a mild winter climate (New Delhi, India) and a harsh winter climate (Boulder, Colo.,U.S.A.). The results indicate that, for a mild winter climate, a floor area equal to that of the glazed area is able to provide comfortable conditions, while for a harsh winter climate, the floor area/glazed area ratio may be 1 2 or 3 4 , and auxiliary energy also has to be used.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.