Abstract

The oxygenate water level is an important adjustment parameter in the operation of the fire generator set, and the water level may result in the safety of the water pump. The high water level will not only affect the oxygen effect, but it is also possible to cause the water shot to the steam turbine to cause a water shot or give the water tank full water, oxygenate vibration, drain and vapor with water. When the load is low (generally 35% rated load), the oxygenate water level is controlled by large and small valve, condensate pump variable frequency control condensed water drum pressure. When the unit load is high (greater than 35 rated load), the oxygenate water level is controlled by the condensed water pump, the large valve and small valve controls condensed water drum pressure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.